General specifications:
- EEMAC G8-3.3 and C22.2 no 31
- Low voltage (> 750V)
- Metal Enclosed designation
- Maximum rated current ± 5000A
- Noninsulated high voltage bus bars (can be insulated on request)
- Vacuum draw-out or fixed circuit breaker (if vacuum draw-out, this one
is provided with shutters
protecting the parts in a draw out position)
- No separation between the different undervoltage comparments, except for
the circuit breaker and
the control compartment, if required. A higher compartmentation than required
by the standards can
be provided. For example: separate cables from the main bus
- The protection unit is usually integrated to the circuit breaker. Instrumentation
can be added in the circuit breaker compartment door or in the control compartment
- Metal enclosure is grounded and completely closed on sides and on top
generally in gauges 12
- Mechanical interlock allowing no access to undervoltage parts of accessible
elements
- Control wire, if required, TBS or SIS, 14 AWG min.