General specifications:
- EEMAC G8 3.2, C22.2 no 31
- Medium voltage (5 kV to 35 kV)
- Metal Clad designation
- Maximum rated current ±4000A
- High voltage bus bars completely insulated
- Bushings are used when bus bars strut a metal compartment
- The vacuum draw-out circuit breaker has shutters protecting parts in a draw-out
position
- All compartments are separated with grounding steel metal compartments (steel
gauge 11)
- Low voltage accessories (relays, measuring instrument, etc.) are separated
from undervoltage parts by a control compartment
- Metal enclosure is grounded and completely closed on sides and on top, generally
in gauges 12
- Mechanical interlock allowing no access to undervoltage parts of accessible
elements
- Control wire, TBS or SIS, 14 AWG min.
For overall dimensions: